Backflow assembly test · Riverside Dental
ApprovedFiled Aug 28, 2025 by Morgan Marsh, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 28, 2025
- Assembly type
- RP
- Serial number
- A957460
- Size
- 1 1/2
- Test gauge serial
- G-3137
- Gauge calibration date
- Jun 23, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-36-01174
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.