Backflow assembly test · 1922 Mill Creek Ln
ApprovedFiled Sep 26, 2024 by Morgan Marsh, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 26, 2024
- Assembly type
- DC
- Serial number
- K309481
- Size
- 1
- Test gauge serial
- G-7538
- Gauge calibration date
- Jun 12, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-79-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.