Jefferson County, ALCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7313 Orchard Trl

Approved

Filed Mar 15, 2025 by Alex Benton, Northstar Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 15, 2025
Assembly type
RP
Serial number
B520189
Size
1
Test gauge serial
G-8727
Gauge calibration date
Aug 30, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-88-01069
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7313 Orchard Trl
Owner: Parker Pruitt
Parcel 073-88-01069