Backflow assembly test · Main Street Diner
ApprovedFiled Sep 10, 2025 by Drew Stroud, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Sep 10, 2025
- Assembly type
- RP
- Serial number
- K927199
- Size
- 1
- Test gauge serial
- G-6084
- Gauge calibration date
- Jan 1, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-31-01335
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.