← Backflow review queue
Backflow assembly test · Maple Leaf Apartments
ApprovedFiled Oct 30, 2024 by Drew Stroud, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Oct 30, 2024
- Assembly type
- RP
- Serial number
- W921237
- Size
- 2
- Test gauge serial
- G-1856
- Gauge calibration date
- Sep 28, 2024
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-61-01302
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6254 Quarry Rd
Owner: Benton Holdings LLC
Parcel 005-61-01302