Backflow assembly test · Maple Leaf Apartments
ApprovedFiled Nov 30, 2025 by Taylor Vance, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Nov 30, 2025
- Assembly type
- RP
- Serial number
- W921237
- Size
- 2
- Test gauge serial
- G-9791
- Gauge calibration date
- Apr 17, 2025
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-61-01302
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.