Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Medical Offices

Approved

Filed Jul 6, 2025 by Taylor Vance, Northstar Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jul 6, 2025
Assembly type
DC
Serial number
W465856
Size
1 1/2
Test gauge serial
G-1277
Gauge calibration date
Nov 17, 2024
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-71-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4183 Hickory Trl
Owner: Kessler Holdings LLC
Parcel 005-71-01296