Backflow assembly test · 3021 Mill Creek Ct
ApprovedFiled Jan 2, 2024 by Hayden Stroud, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Jan 2, 2024
- Assembly type
- RP
- Serial number
- Z892740
- Size
- 1
- Test gauge serial
- G-8421
- Gauge calibration date
- Jul 12, 2023
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-50-01320
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.