Coconino County, AZReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8889 Mill Creek Trl

Approved

Filed Nov 3, 2024 by Cameron Okafor, Northstar Backflow Testing · filed from phone

Report

Date of service
Nov 3, 2024
Assembly type
RP
Serial number
Z435246
Size
1
Test gauge serial
G-1627
Gauge calibration date
May 22, 2024
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Okafor, current on the service date
  • All required fields present
  • Address matches parcel 005-78-01231
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8889 Mill Creek Trl
Owner: Sam Okafor
Parcel 005-78-01231