Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2156 Spring Branch Ln

Approved

Filed Sep 17, 2026 by Cameron Okafor, Northstar Backflow Testing · filed from phone

Report

Date of service
Sep 17, 2026
Assembly type
RP
Serial number
Z454297
Size
3/4
Test gauge serial
G-8210
Gauge calibration date
Aug 11, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-42-01148
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2156 Spring Branch Ln
Owner: Jordan Ashby
Parcel 005-42-01148