Backflow assembly test · 6306 Laurel Ln
ApprovedFiled Dec 13, 2025 by Drew Stroud, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Dec 13, 2025
- Assembly type
- RP
- Serial number
- A597095
- Size
- 1
- Test gauge serial
- G-7958
- Gauge calibration date
- Sep 18, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-37-01093
- Readings in range, no flags
- Result: passing. Next due date resets when approved.