Maricopa County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7986 Quarry Rd

Approved

Filed Sep 2, 2023 by Logan Benton, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Sep 2, 2023
Assembly type
RP
Serial number
W637377
Size
3/4
Test gauge serial
G-8280
Gauge calibration date
Mar 18, 2023
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-85-01328
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7986 Quarry Rd
Owner: Shawn Harlow
Parcel 013-85-01328