Backflow assembly test · 8076 Spring Branch Dr
ApprovedFiled Sep 24, 2025 by Logan Benton, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 24, 2025
- Assembly type
- RP
- Serial number
- B817675
- Size
- 3/4
- Test gauge serial
- G-1707
- Gauge calibration date
- May 26, 2025
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-53-01133
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.