Backflow assembly test · 3521 Stone Gate Ct
ApprovedFiled Oct 10, 2026 by Hayden Stroud, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Oct 10, 2026
- Assembly type
- RP
- Serial number
- W939117
- Size
- 3/4
- Test gauge serial
- G-8398
- Gauge calibration date
- Mar 22, 2026
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 019-56-01187
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3521 Stone Gate Ct
Owner: Drew Hollins
Parcel 019-56-01187