Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 703 Meadow Lark Ct

Approved

Filed Jul 27, 2026 by Jamie Pruitt, Lakeside Backflow Testing · filed from phone

Report

Date of service
Jul 27, 2026
Assembly type
RP
Serial number
W989396
Size
1
Test gauge serial
G-8090
Gauge calibration date
Jun 24, 2026
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-48-01182
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

703 Meadow Lark Ct
Owner: Logan Calloway
Parcel 019-48-01182