Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9435 Fox Run Ln

Approved

Filed Oct 24, 2025 by Hayden Stroud, Patriot Backflow Testing · filed from phone

Report

Date of service
Oct 24, 2025
Assembly type
RP
Serial number
W328783
Size
1
Test gauge serial
G-7968
Gauge calibration date
May 9, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-13-01210
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9435 Fox Run Ln
Owner: Reese Calloway
Parcel 019-13-01210