Backflow assembly test · 5014 Turkey Hill Way
ApprovedFiled May 13, 2024 by Logan Vance, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- May 13, 2024
- Assembly type
- RP
- Serial number
- B193845
- Size
- 3/4
- Test gauge serial
- G-9624
- Gauge calibration date
- Aug 19, 2023
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 019-70-01344
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.