Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3043 Mill Creek Ct

Approved

Filed Jan 30, 2024 by Morgan Calloway, Lakeside Plumbing & Backflow · filed from phone

Report

Date of service
Jan 30, 2024
Assembly type
DC
Serial number
W588128
Size
1
Test gauge serial
G-7304
Gauge calibration date
Oct 3, 2023
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-77-01127
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3043 Mill Creek Ct
Owner: Morgan Whitcomb
Parcel 019-77-01127