Backflow assembly test · 6012 Cedar Hollow Trl

Approved

Filed May 28, 2024 by Drew Stroud, Clearwater Backflow Testing · filed from phone

Report

Date of service
May 28, 2024
Assembly type
DC
Serial number
Z561819
Size
1
Test gauge serial
G-8363
Gauge calibration date
Jan 3, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-88-01056
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6012 Cedar Hollow Trl
Owner: Logan Benton
Parcel 021-88-01056