← Backflow review queue
Backflow assembly test · 4092 Mill Creek Rd
ApprovedFiled Dec 9, 2024 by Parker Ramirez, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Dec 9, 2024
- Assembly type
- RP
- Serial number
- B220327
- Size
- 3/4
- Test gauge serial
- G-9056
- Gauge calibration date
- Nov 4, 2023
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 021-24-01035
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.