Pinal County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2065 Meadow Lark Rd

Approved

Filed Nov 20, 2024 by Riley Pruitt, Heritage Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 20, 2024
Assembly type
RP
Serial number
B326219
Size
3/4
Test gauge serial
G-2278
Gauge calibration date
Apr 3, 2024
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-22-01149
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2065 Meadow Lark Rd
Owner: Jordan Vance
Parcel 021-22-01149