Pinal County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 425 Hickory Rd

Approved

Filed Jan 17, 2024 by Riley Pruitt, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Jan 17, 2024
Assembly type
RP
Serial number
B140119
Size
1
Test gauge serial
G-4227
Gauge calibration date
Dec 6, 2023
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-49-01180
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

425 Hickory Rd
Owner: Avery Brandt
Parcel 021-49-01180