Backflow assembly test · 425 Hickory Rd
ApprovedFiled Jan 21, 2025 by Drew Stroud, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jan 21, 2025
- Assembly type
- RP
- Serial number
- B140119
- Size
- 1
- Test gauge serial
- G-7587
- Gauge calibration date
- Apr 19, 2024
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 021-49-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.