Yavapai County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Self Storage

Approved

Filed Jul 30, 2025 by Riley Nguyen, Clearwater Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jul 30, 2025
Assembly type
RP
Serial number
Z380413
Size
4
Test gauge serial
G-9409
Gauge calibration date
Jun 30, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 025-22-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9830 Turkey Hill Dr
Owner: Nguyen Holdings LLC
Parcel 025-22-01279