← Backflow review queue
Backflow assembly test · 1259 Quarry Dr
ApprovedFiled Nov 14, 2025 by Cameron Danner, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 14, 2025
- Assembly type
- PVB
- Serial number
- A714057
- Size
- 3/4
- Test gauge serial
- G-8230
- Gauge calibration date
- Mar 22, 2025
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-91-01038
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1259 Quarry Dr
Owner: Emerson Fairley
Parcel 025-91-01038