← Backflow review queue
Backflow assembly test · 5931 Turkey Hill Way
ApprovedFiled Jul 20, 2026 by Quinn Wexler, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Jul 20, 2026
- Assembly type
- RP
- Serial number
- W427326
- Size
- 1
- Test gauge serial
- G-7667
- Gauge calibration date
- Nov 21, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-48-01357
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5931 Turkey Hill Way
Owner: Reese Fairley
Parcel 027-48-01357