← Backflow review queue
Backflow assembly test · 3671 Old Church Ln
ApprovedFiled Oct 11, 2024 by Logan Whitcomb, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 11, 2024
- Assembly type
- RP
- Serial number
- Z213524
- Size
- 3/4
- Test gauge serial
- G-4611
- Gauge calibration date
- Jan 19, 2024
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-23-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3671 Old Church Ln
Owner: Sam Pruitt
Parcel 027-23-01257