Backflow assembly test · 5140 Meadow Lark Ln
ApprovedFiled Nov 11, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 11, 2026
- Assembly type
- RP
- Serial number
- W965277
- Size
- 1
- Test gauge serial
- G-9368
- Gauge calibration date
- May 27, 2026
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-13-01239
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.