Backflow assembly test · Hilltop Diner
ApprovedFiled Oct 22, 2023 by Jordan Pruitt, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Oct 22, 2023
- Assembly type
- RP
- Serial number
- Z871861
- Size
- 2
- Test gauge serial
- G-4905
- Gauge calibration date
- Jul 20, 2023
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-78-01070
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.