Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 646 Turkey Hill Rd

Approved

Filed May 4, 2025 by Logan Whitcomb, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
May 4, 2025
Assembly type
PVB
Serial number
K541454
Size
3/4
Test gauge serial
G-6237
Gauge calibration date
Oct 7, 2024
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-63-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

646 Turkey Hill Rd
Owner: Shawn Brandt
Parcel 027-63-01327