Backflow assembly test · Maple Leaf Diner
ApprovedFiled Jun 6, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 6, 2026
- Assembly type
- DC
- Serial number
- W329089
- Size
- 1 1/2
- Test gauge serial
- G-4778
- Gauge calibration date
- Dec 18, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-55-01094
- Readings in range, no flags
- Result: passing. Next due date resets when approved.