Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8240 Fox Run Trl

Approved

Filed Oct 31, 2025 by Jordan Pruitt, Keystone Backflow Testing · filed from phone

Report

Date of service
Oct 31, 2025
Assembly type
RP
Serial number
Z240158
Size
3/4
Test gauge serial
G-6852
Gauge calibration date
Jan 10, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-40-01312
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8240 Fox Run Trl
Owner: Reese Marsh
Parcel 027-40-01312