Backflow assembly test · 9563 Turkey Hill Dr
Needs reviewFiled Nov 24, 2026 by Parker Danner, Valley Backflow Testing · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- A279302
- Size
- 3/4
- Test gauge serial
- G-4247
- Gauge calibration date
- Oct 22, 2026
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-32-01183
- Readings in range, no flags
- Result: passing. Next due date resets when approved.