← Backflow review queue
Backflow assembly test · Golden Diner
ApprovedFiled May 3, 2025 by Emerson Brandt, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 3, 2025
- Assembly type
- RP
- Serial number
- B837086
- Size
- 1 1/2
- Test gauge serial
- G-8324
- Gauge calibration date
- Jan 17, 2024
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-30-01234
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4954 Orchard Dr
Owner: Harlow Holdings LLC
Parcel 007-30-01234