Benton County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Market

Approved

Filed Apr 20, 2026 by Parker Danner, Valley Backflow Testing · filed from phone

Report

Date of service
Apr 20, 2026
Assembly type
RP
Serial number
B828295
Size
2
Test gauge serial
G-1615
Gauge calibration date
Nov 8, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-83-01007
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9018 Turkey Hill Ct
Owner: Wexler Holdings LLC
Parcel 007-83-01007