Backflow assembly test · Station Medical Offices

Approved

Filed Jun 30, 2025 by Parker Danner, Valley Backflow Testing · filed from phone

Report

Date of service
Jun 30, 2025
Assembly type
RP
Serial number
Z390697
Size
2
Test gauge serial
G-7839
Gauge calibration date
Dec 26, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-15-01295
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.