Benton County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Grill

Approved

Filed Nov 20, 2025 by Parker Danner, Valley Backflow Testing · filed from phone

Report

Date of service
Nov 20, 2025
Assembly type
RP
Serial number
W347786
Size
1 1/2
Test gauge serial
G-8519
Gauge calibration date
Jul 14, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-14-01328
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7687 Orchard Trl
Owner: Harlow Holdings LLC
Parcel 007-14-01328