Benton County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Medical Offices

Approved

Filed Jul 16, 2024 by Emerson Brandt, Clearwater Backflow Testing · filed from phone

Report

Date of service
Jul 16, 2024
Assembly type
RP
Serial number
B529532
Size
1
Test gauge serial
G-9231
Gauge calibration date
Dec 21, 2023
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-88-01349
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7557 Meadow Lark Trl
Owner: Nguyen Holdings LLC
Parcel 007-88-01349