← Backflow review queue
Backflow assembly test · Blue Heron Dental
ApprovedFiled Nov 20, 2025 by Emerson Brandt, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Nov 20, 2025
- Assembly type
- RP
- Serial number
- A544839
- Size
- 2
- Test gauge serial
- G-6467
- Gauge calibration date
- Mar 28, 2025
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-36-01140
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.