Backflow assembly test · 8360 Quarry Way
ApprovedFiled Dec 21, 2024 by Parker Danner, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Dec 21, 2024
- Assembly type
- DC
- Serial number
- A900677
- Size
- 1
- Test gauge serial
- G-1271
- Gauge calibration date
- Mar 12, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-53-01223
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.