Faulkner County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Apartments

Approved

Filed May 31, 2024 by Drew Vance, Clearwater Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
May 31, 2024
Assembly type
DC
Serial number
K101643
Size
4
Test gauge serial
G-2628
Gauge calibration date
Jul 24, 2023
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 045-13-01098
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7407 Old Church Dr
Owner: Marsh Holdings LLC
Parcel 045-13-01098