Faulkner County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Riverside Apartments

Approved

Filed Jul 27, 2025 by Reese Ellery, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Jul 27, 2025
Assembly type
RP
Serial number
K445404
Size
1
Test gauge serial
G-9098
Gauge calibration date
Apr 5, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 045-89-01197
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1080 Pine Knoll Ln
Owner: Vance Holdings LLC
Parcel 045-89-01197