Backflow assembly test · 4239 Spring Branch Rd
ApprovedFiled Sep 24, 2024 by Cameron Whitcomb, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 24, 2024
- Assembly type
- DC
- Serial number
- K423960
- Size
- 1
- Test gauge serial
- G-9927
- Gauge calibration date
- Jun 15, 2023
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-14-01266
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.