Backflow assembly test · Main Street Pizza
ApprovedFiled Sep 18, 2026 by Drew Vance, Clearwater Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Sep 18, 2026
- Assembly type
- RP
- Serial number
- W372001
- Size
- 1 1/2
- Test gauge serial
- G-3010
- Gauge calibration date
- Jun 25, 2026
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 045-97-01021
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
950 Spring Branch Ct
Owner: Harlow Holdings LLC
Parcel 045-97-01021