Backflow assembly test · 3726 Laurel Way

Approved

Filed Sep 11, 2025 by Hayden Okafor, Northstar Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Sep 11, 2025
Assembly type
RP
Serial number
W976591
Size
1
Test gauge serial
G-3008
Gauge calibration date
Jun 30, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
2.7 psid
Relief valve opened at
3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-40-01297
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3726 Laurel Way
Owner: Sam Ramirez
Parcel 131-40-01297