Backflow assembly test · 7074 Spring Branch Way
ApprovedFiled Oct 24, 2026 by Hayden Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Oct 24, 2026
- Assembly type
- RP
- Serial number
- K857914
- Size
- 3/4
- Test gauge serial
- G-6483
- Gauge calibration date
- Apr 28, 2026
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-46-01095
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7074 Spring Branch Way
Owner: Logan Lindqvist
Parcel 131-46-01095