Sebastian County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Apartments

Approved

Filed Aug 13, 2025 by Hayden Okafor, Northstar Backflow Testing · filed from phone

Report

Date of service
Aug 13, 2025
Assembly type
RP
Serial number
Z996926
Size
4
Test gauge serial
G-1425
Gauge calibration date
Nov 15, 2024
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-24-01265
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1057 Pine Knoll Dr
Owner: Danner Holdings LLC
Parcel 131-24-01265