Backflow assembly test · Two Rivers Grill

Approved

Filed Jun 18, 2024 by Hayden Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Jun 18, 2024
Assembly type
RP
Serial number
B422281
Size
4
Test gauge serial
G-4104
Gauge calibration date
Feb 23, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-44-01287
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.