Backflow assembly test · 4519 Mill Creek Rd
ApprovedFiled Dec 2, 2024 by Hayden Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Dec 2, 2024
- Assembly type
- RP
- Serial number
- W641417
- Size
- 3/4
- Test gauge serial
- G-7035
- Gauge calibration date
- Jun 10, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-17-01202
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4519 Mill Creek Rd
Owner: Reese Pruitt
Parcel 131-17-01202