Backflow assembly test · 4519 Mill Creek Rd
ApprovedFiled Dec 10, 2025 by Hayden Okafor, Northstar Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Dec 10, 2025
- Assembly type
- RP
- Serial number
- W641417
- Size
- 3/4
- Test gauge serial
- G-6593
- Gauge calibration date
- Aug 4, 2024
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-17-01202
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4519 Mill Creek Rd
Owner: Reese Pruitt
Parcel 131-17-01202